Jonathon Pullen
Technical Services Manager
Gulf Coast District
The Infamous E1: Part 2
E1 fault code on Ductless equipment is communication fault between the indoor and outdoor units.
When the E1 code shows up on the indoor display board, the coms have failed and the systems have stopped working. Until this problem is fixed, the system will remain off.
Start trouble shooting this problem at the outdoor by taking a DCV reading on L2 and S or 2 and 3 depending on how the unit is labeled. Take a DCV reading on the terminals for the indoor unit wires.
Good coms volts look like + to – 50 volts fluctuation.
If you see a fixed negative or a small amount of fluctuating volts staying in the negative, the indoor board has failed.
If you see a fixed positive volt reading or a fluctuating positive reading the outdoor board is bad.
The reactor also needs to be checked. Check the reactor with the wires off and ohm it out. The ohm reading should be .1-1 ohm and should not be grounded.
More to explore
Flame Simulator
You go on a no heat call on a gas pack/ furnace. All the burners ignite, but then go out followed by
DUCKT-STRIP Wiring
DUCKT-STRIP wire is a great product for ductless units when used properly. The wire is used to power and communicate between the
Totaline Slime Prevention & Removal
TIC2021-0006 states that a slime has been detected in condensate lines, traps, drains and pans. From TIC: “The slime is what is